The fluid in the line must match the medium calibrated in the selected Solenoid Valve Body series.
The temperature of the fluid must be less than the calibration temperature of the solenoid valve selected.
OEM Solenoid Valve Body allow liquid viscosity to be generally below 20 CST, greater than 20 CST should be noted.
Working pressure difference, the maximum pressure difference of the pipeline should be less than 0.04MPa, such as ZS, 2W, ZQDF, ZCM series and other direct-acting and step-by-step direct-acting type; when the minimum working pressure difference is greater than 0.04MPa, the pilot type can be used. Differential) Solenoid valve; the maximum working pressure difference should be less than the maximum calibration pressure of the solenoid valve; the general solenoid valve is one-way operation, so pay attention to whether there is a back pressure difference, if there is a check valve installed.
When the fluid cleanliness is not high, the filter should be installed in front of the solenoid valve. Generally, the solenoid valve requires good cleanliness for the medium.
Pay attention to the flow aperture and the diameter of the nozzle; the solenoid valve is generally only controlled by the two-position switch; if necessary, please install the bypass tube for easy maintenance; when there is water hammer, customize the opening and closing time of the solenoid valve.
Pay attention to the influence of ambient temperature on the solenoid valve
The power supply current and power consumption should be selected according to the output capacity. The power supply voltage is generally allowed to be ±10%. It must be noted that the VA value is higher when the AC starts.